4007-9101 SIMPLEX 4007ES HYBRID FACP, RED.
4007ES HYBRID FACP, RED,
BRAND: SIMPLEX, ORIGIN: USA, CERTIFICATION: UL LISTED 4007-9101
4007-9101 Simplex ES Series Fire Detection and Control Units provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. Panels can be configured for stand-alone or networked fire control operations. The convenient and intuitive color touchscreen provides easy access for typical system response actions and for detailed system review or configuration updates with password control to limit user access. Flexible for new and retrofit applications. Standard conventional IDCs and addressable IDNet+ communications provide flexibility for both new and retrofit systems. IDC and NAC end-of-line resistor values are selectable to match a wide range of existing initiating device circuits and notification appliance circuits.
Compatible with Simplex ES Net and 4120 fire alarm networks Satisfies a variety of new and retrofit applications 4.3 in. (109 mm) diagonal color touchscreen display:

  • Provides detailed system status and point information
  • Supports dual language selection, including Unicode character languages
  • A custom background display appears when an operation is normal

Eight Point Zone/Relay Module:

  • Each point is selectable as an IDC input or Relay output, Class A IDCs require two points (one out and one return); one module is standard, up to three additional modules can be field installed for a total of four 8 point zone/relay modules per system.
  • Each point on the IDC/Relay Module can be configured as a control relay rated 2 A @ 30 VDC (resistive) as either normally open or normally closed.
  • Can be powered directly from the power supply or through the optional 25 VDC Regulator Module.
  • IDC end-of-line resistor value can be selected from a wide range of resistance values for retrofit convenience.

Electrically isolated IDNet+ addressable initiating device SLC:

  • Provides built-in short circuit isolation for monitoring and control of TrueAlarm analog sensors and IDNet communications monitoring and control devices; for use with either shielded or unshielded, twisted or untwisted single pair wiring; outputs are Class A or Class B.
  • Standard panel SLC provides up to 100 addressable points; optional additional loop expansion modules provide an additional isolated loop with short circuit isolation for the IDNet+ channel; each loop expansion module also provides an additional 75 addressable points.

Power Supply Features:

  • Four Notification Appliance Circuits (NACs) selectable as Class A or Class B with 6 A total available current.
  • NAC end-of-line resistor value can be selected from a wide range of resistance values for retrofit convenience.
  • Additional notification power capacity is available using the 4009 IDNet NAC Extender.
  • Battery backup charging of up to 33 Ah; up to 18 Ah for cabinet mounted batteries a